'Indian - CAB' 1.1 KV ANNEALED HIGH CONDUCTIVITY SOLID COPPER CONDUCTOR, 1.5 Sq. mm., PVC INSULATED, INNER SHEATHED, ARMOURED/UNARMOURED PVC SHEATHED CABLES CONFORMING TO IS : 1554(PART-I) AMENDED UPTO DATE

No. of
cores
Nomi.
thick-
ness

of
Insu-

lation
mm
Min.
thick-
ness

of Inner
sheath
mm
Armour Nomi.
Sheath
thick-
ness

for
Un-
armd.

mm
Min.
Sheath
thick-
ness

for
Armd.

mm
Approx.
overall
diameter
Approx
wt. of
cable
Max.
DC

con-
ductor

resis-
tance

at 20° C
Ohm/km
Current Ratings
Gal.
Round
Steel
Wira
Nomi-
nal
Dia.
mm
Gal.
Flat
Steel
Strip
Nominal
Thick-

ness
mm
Un-
armd

mm
Armd.
mm
Approx
wt. of
cable
Armd.
kg/km
Direct
in
Ground
Amps
In
Ducts
Amps
In
Air
Amps
2
0.8
0.3
1.4
-
1.8
1.24
10.4
12.0
170
390
12.1
23
20
20
3
0.8
0.3
1.4
-
1.8
1.24
10.9
12.7
195
430
12.1
21
17
17
4
0.8
0.3
1.4
-
1.8
1.24
11.7
13.3
225
480
12.1
21
17
17
5
0.8
0.3
1.4
-
1.8
1.24
12.6
14.2
275
560
12.1
21
17
17
6
0.8
0.3
1.4
-
1.8
1.24
13.4
15.0
325
625
12.1
15
13
13
7
0.8
0.3
1.4
-
1.8
1.24
13.4
15.0
345
645
12.1
14
13
13
10
0.8
0.3
1.4
-
1.8
1.40
16.5
18.2
460
810
12.1
13
11
11
12
0.8
0.3
-
0.8
1.8
1.24
17.0
17.3
520
815
12.1
12
10
10
14
0.8
0.3
-
0.8
1.8
1.40
17.7
18.3
580
885
12.1
11
10
10
16
0.8
0.3
-
0.8
2.0
1.40
19.0
19.1
680
980
12.1
11
9
9
19
0.8
0.3
-
0.8
2.0
1.40
19.9
20.0
780
1100
12.1
10
9
9
24
0.8
0.3
-
0.8
2.0
1.40
23.0
23.0
950
1300
12.1
9
8
8
30
0.8
0.3
-
0.8
2.0
1.40
24.2
24.3
1150
1540
12.1
9
7
7
37
0.8
0.3
-
0.8
2.0
1.40
26.0
26.0
1350
1800
12.1
8
7
7
61
0.8
0.4
-
0.8
2.2
1.40
32.7
38.6
2100
2670
12.1
7
6
6

Unarmd :- Unarmoured 
Armd :- Armoured
Nomi :- Nominal